PRODUCTS
SC 10.1 GHM Gas /Heavy oil modulation Monobloc Burner
Technical information

SC. 10.1 GHM

Capacity
kW/hMin850
Max2750
kcal/hMin731.000
Max2.365.000

m3/h

l/h

Min88
Max286
Min76
Max246
Power Supply
3N-50 Hz  380V
Motor kW
3
Pump Motor kW
1,1
Heater12
Gas Input Pressure
21-300
More information 1. The following fuels can be used:
Natural gas PCI 6,99…11,39 kWh/Nm3.
LPG, 25,89 kWh/Nm3
2. It is suitable for steam, hot water boiler, ovens, driers, heat oil generators, etc.
3. The flame can be adjusted according to the combustion chamber.
4. Burning hood, ventilation system, control panel, gas pipe could be selected according to special conditions of each installation.
5. The 1/ 10 ,in gas and 1/5 in light oil regulation of the electronic modulation power, is really advantageous compared to our rivals.
6. Flame monitoring is easy and reliable thanks to the UV sensor.
7. A customized type of sensor is used for sequentially installment of several generators
8. The facility of heating and the use of preheated combustion air while enabling energy saving in increasing the efficiency of the burning through economiser used by the system.
9. It enables flame control at each point between minimum and maximum power. It enables flame control at each point between minimum and maximum power.
10. It has the characteristics of proper functioning in different combustion chambers.
11. Reduces the specific emission amount of nitric oxide (NOx) gas to a minimum by obtaining an optimum mixture of combustible air thanks to the customized design of its combustion hood.
12. It provides easy installation and operating conditions in confined spaces thanks to its compact dimensions.
13. It enables operation in high backpressure combustion chambers by placing a high-pressure ventilation system.
14. Standard protection of IP 54 mechanical parts.
15. IP 65 protection on demand.
16. Internal or external optional circulation of combustion gases in order to reduce NOx emissions.
17. It includes all the cables and power supply of the burner management system.
18. Includes impermeability control.
19. Compliance with the following directives:
89/336(2004/108)EEC
73/23/EEC
98/37/EEC
EN 676
20. Continuous O2 analyzer in order to sustain extra efficiency.
21. Continuous CO analyzer for precise control system.
22. Speed variant to extend product life cycle.